Could Your Sprinkler System Freeze? A Toronto Property Manager’s Pre-Winter Checklist

Review heating changes, dry-pipe valve-room checks and cold-weather follow-up before winter. Know what to send with a Toronto sprinkler service enquiry.

FC Fire PreventionPublished 3 min read

A vacant unit, failed heater or loading door left open can change the conditions around sprinkler piping. Before Toronto’s colder weather arrives, review those changes with your sprinkler service provider. A pre-winter walk-through should identify concerns and assign follow-up—not become an improvised system test.

1. Check what changed since last winter

Walk the property with the person responsible for building heating. Note vacant spaces, new partitions, altered heating schedules and doors that no longer close properly. Pay attention to areas where staff have reported cold conditions, rather than assuming the office thermostat represents the whole building.

Record the location, what changed and who will investigate it. Share relevant drawings and the latest sprinkler inspection report. Confirm the installed system type from records or your service provider; do not guess from the appearance of exposed piping.

2. Review heating changes before making them

Ontario Fire Code Article 6.5.1.4 addresses equipment or occupancy changes that could expose wet-pipe sprinklers to temperatures below 4°C. Those changes require prior provisions to alter the system to prevent freezing. This is not a suggestion to set every thermostat to 4°C: the conditions at the sprinklers matter.

If a tenant is leaving, discuss the proposed heating arrangements before reducing heat. Ask who will check the affected spaces, receive a heating-failure report and arrange corrective work. Include weekends and holidays in that handover.

3. Do not assume a dry-pipe system needs no winter attention

Article 6.5.3.3 requires dry-pipe valve rooms or enclosures in unheated buildings to be checked as often as necessary when the outside temperature is below 0°C, to prevent freezing. It does not give a single check frequency suitable for every property.

Ask the responsible service provider to confirm the property’s cold-weather checks, who is trained to perform them and how concerns should be escalated. Keep the checking instructions available to relief staff. Do not drain piping, adjust valves or change system settings as part of an informal walk-through.

4. Give each concern an owner and a response

A useful management log can be simple:

  • Exact room, unit or equipment location.
  • Observed concern, date and any safely obtained photograph.
  • Person responsible for investigating or arranging service.
  • Action due date and an after-hours contact.
  • Completion evidence and any remaining restriction.

For suspected freezing, leakage or a system fault, contact the responsible building personnel and service provider promptly. Do not operate control valves to investigate or improvise a thawing method. Toronto’s general frozen-pipe advice warns against open flames; sprinkler concerns need system-specific professional attention. Follow the property’s emergency procedures; for a fire or immediate danger, call 911.

If work will interrupt sprinkler protection, agree the shutdown arrangements with the service provider before work begins. Article 6.5.2.1 requires notification to the Chief Fire Official for alterations, additions or repairs involving an interruption.

5. Request a defined sprinkler service scope

Contact FC Fire Prevention with the property address, system type if known, affected locations, heating changes and recent inspection findings. Ask whether you need a sprinkler inspection or maintenance visit, an investigation, or a specific repair proposal. Include access arrangements and the person authorized to approve work.

A winter checklist helps coordinate people and information. It does not establish that a system is operational or replace its required inspection, testing and maintenance.

Sources checked October 30, 2026: Ontario Fire Code, Division B, Articles 6.5.1.4, 6.5.3.3 and 6.5.2.1; see also the official 2026 Fire Code Compendium. General planning guidance, not a site-specific compliance determination or operating procedure.